AVDA



Self-acting differential pressure controllers primarily for use in district heating and central heating systems.

They are usually installed on by-pass to control constant flow in the main pipe.


AVDA

Technical data



Code No.DNkvs
(m3/h)
PN
(bar)
tmax
(°C)
Connection typeInstallation placeSetting typeMin. Dp set
(bar)
Max. Dp set
(bar)

AVDA

003N0038 151.910130Int. threadBypassAdjustable0.11.2
003N0039 203.410130Int. threadBypassAdjustable0.11.2
003N0040 255.510130Int. threadBypassAdjustable0.11.2